Model |
MTS30K |
MTS40K |
MTS50K |
MTS60K |
MTS80K |
MTS100K |
MTS120K |
Rated Power |
30KW |
40KW |
50KW |
60KW |
80KW |
100KW |
120KW |
Max. input current |
40A |
56A |
71A |
102A |
133A |
164A |
195A |
Rated DC input |
0-550Vdc |
Grid AC input |
Three Phase 380V-415Vac/50hz (The Inverter will use the grid power as standby power , this inverter can not send any power into utility grid) |
Working |
The DC main power supply, the grid AC for standby power supply and automatic switching |
Power Factor |
0.92(with input filter) |
AC output |
Phase No.: Three Phase (3W+N+G) |
Frequency : 50HZ /60HZ ; frequency precision ¡À0.5%
(in-phase with the one when supply by grid power ) |
Wave form: Pure sine wave
Linear load THD£¼3%£»Nonlinear load£ºTHD£¼5% |
Power factor : 0.8 lag |
Transient state of dynamic voltage : 0-100%load change,£¼10% ¡À5% |
Recovery time of transient state : £¼20ms |
Unbalance of three-phase voltage: £¼¡À3%(unbalanced load)£»£¼¡À1%(balanced load) |
Switch time |
0-4milliseconds |
Time of static switch |
£¼4 milliseconds |
Efficiency |
£¾81£¥ |
Noise (1m distance ) |
£¼55db |
Protection |
Protection against over-current , , over-voltage, overload |
LED indicator light |
The states of mains supply , inversion , overload and battery etc |
LCD liquid crystal display |
Manufacturer, Models , supply or inversion predicament , input/output voltage , frequency , battery voltage and load percentage |
Warn |
Low voltage of battery : pulsed sound per second |
Overload : successive |
Machine fault : successive |
Computer control interface (with RS232 Interface ) |
Complete monitoring and controlling the working state of machine , warning of mains supply failure and low
voltage of battery , saving documents as well as closing the machine
1) Telemeter the input/output voltage and frequency of machine, load , battery capacity which will be shown appropriately on PC machine
2) Monitoring the working state of machine automatically
3) Preset the machine ¡®s function of starting & closing machine through PC
4) It can automatically save documents , closed PC and then closed itself before the battery power off |
|
Temperature: 0-40oC |
Using environment |
Relative Humidity : 30%-90% no condensation |
Altitude : £¼1000m (the power will drop 1% per increase of 100m , Max altitude : 4000m) |
Packing Size |
MTS30K |
785 x 520 x 1400mm (LX W X H) |
360KGS |
MTS40K |
785 x 520 x 1400mm (LX W X H) |
420KGS |
MTS50K |
903 X 740 X 1370mm (LX W X H) |
530KGS |
MTS60K |
1000 x 740 x1370mm(LX W X H) |
560KGS |
MTS80K |
1000 x 740 x1370mm(LX W X H) |
690KGS |
MTS100K |
1000 x 740 x1370mm(LX W X H) |
840KGS |
MTS120K |
1000 x 740 x1370mm(LX W X H) |
880KGS |